• 3C3 series (3Phase), high frequency online UPS 20 ~ 180 kVA (tower/ rack type)
    Basic Features

    1. 3 phase input, 3 phase output pure online dual conversion products, support 380 / 400 / 415V, 50 / 60Hz power grid system, to provide the best power quality and load protection.

    2. Super load adaptability, super overload and short circuit capacity.

    3. Ultra-wide input voltage and frequency range, adapt to the harsh power grid environment, adapt to the use of various fuel generators.

    4. The input power factor is up to 0.99, the input harmonic current is less than 3%, and the overall efficiency is greater than 95%. Green, high efficiency and energy saving.

    5. DSP full digital control realizes full digital control of power conversion links such as rectification, inversion and charge and discharge.

    6. Digital cycle control technology, high reliability.

    7. Intelligent battery management scheme to prolong the battery life.

    8. The system adopts a modular design, with a stable and reliable performance.

    9. All the fans in the system are redundant in design, which greatly improves the reliability of the system.

    10.The EPO emergency shutdown function can be realized.

    11.Ultra-long average failure-free time (>200,000 hours) and ultra-low average maintenance time (<0.5 hours).

    12.Rich accessories: dust net, SNMP network communication card, lightning protection module, battery temperature compensator, mobile phone SMS alarm.

    13.All circuit boards adopt three-proof technology.

    14.Traditional modular UPS can be replaced by parallel, saving the high cost of modular cabinet.

    15.7-inch real color touch screen (rack type LCD display) enables users to more intuitively understand the working state and operating parameters of UPS, such as input and output voltage and frequency, load size, battery capacity, machine temperature, etc., so that all operations are clear at a glance.

     

    Technical Specifications

     

    Capacity

    20/30/40kVA

    60/80kVA

    100/120kVA

    150/180kVA

    Import

    Input mode

    Three-phase,   four-wire+grounding

    Rated voltage

    380/400/415Vac

    Voltage range

    138 to 485Vac; 305 to 485Vac, 138 to 305 Vac

    Frequency range

    40~70Hz

    Power factor

    ≥0.99

    Input current harmonics

    3% (100% nonlinear load)

    Bypass range

    Upper limit of bypass protection voltage: 220V: +25% (optional +10%, +15%, +20%);
      230V: +20% (optional +10%, +15%);
      240V: +15% (optional +10%)

    Lower pass protection voltage limit: -45% (optional-10%, -20%, -30%)

    Bypass frequency protection range: ±10%

    Output

    Output method

    Three-phase, four-wire+grounding

    Rated voltage

    380/400/415Vac

    Power factor

    0.9

    Voltage accuracy

    ±1%

    Output   frequency

    Main   mode

    Synchronized with input; output frequency 50 (1±0.02%) Hz beyond ±10% (±1%, ±2%, ±4%, ±5%)

    Battery   mode

    (50/60±0.2%)Hz

    Load peak ratio

    3:1

    Output voltage distortion

    2% linear load, and 4% nonlinear load

    Battery

    Battery voltage

    Voltage optional: ±180V/±192V/±204V/±216V/±228V/±240V/±252V/±264V/±276V/±288V/±300V (30/32/34/36/38/40/42/44/46/48/50)

    360Vdc~600Vdc(30~50sections optional)

    Charging current

    15A max

    15A max

    30A max

    45A max

    Transfer time

    Municipal mode to bypass mode: 0ms (tracking); 

    municipal mode to battery mode: 0ms

    Protect

    Overload capacity

    Load ≤110%, 60mins;125%, 10mins; 150%, 1min; >150%, shutdown immediately.

    Overtemperature   protection

    Normal mode: Switch to the bypass mode; 

    Battery mode: Turn off the output   immediately

    Emergency   Shutdown (EPO)

    Cut off the output immediately

    Communication interface

    USB, RS485, optical coupling node, machine (option), SNMP card (option), Relay   card (option)

    Work   environment

    Working   temperature

    0℃40℃

    Relative humidity

    0~95% with no condensation

    Storage   temperature

    -25℃55℃

    Altitude

    <1500m, exceed 1500m according to GB/T 3859.2

    Physical   characteristics

     Dimensions (D×W×H)

    730×250×530mm(rack type 443×131×580mm)

    850×250×860mm

    850×440×1200mm

    Net weight (Kg)

    45/45.5/45.8

    73/75

    140/149

    190/199

    Operative standard

     YD/T1095-2018

    * The above parameters may be adjusted and changed, please refer to the physical object.

     