• PDM series integrated UPS 20 ~ 150kVA

    Application area

    Small and medium-sized data center, IT computer room, financial institutions, traffic dispatch center, security monitoring, etc.

     

    Functional characteristics

    1.UPS and power distribution of multiple cabinets in one, save space.

    2.138V-485V ultra-wide input voltage range, to adapt to the harsh power grid.

    3.Full modular design of power module, bypass module and control module.

    4.Each module supports hot plug, capacity expansion on demand, and is easy to maintain.

    5.7-inch color touch screen. Circle shape display, easy to operate.

    6.The main input mode is optional, and the number of battery qty 30-50pcs is flexible and adjustable.

    Technical Specifications

     

    Cabinet capacity

    150kVA

    Module capacity

    20kVA,25kVA,30kVA

    Module number

    Maximum 5+1

    input

    Input system

    3-phase+N line+ground wire

    Input voltage

    380/400/415VAC

    Input frequency

    50/60Hz

    Input power factor

    >0.99

    Current-current harmonic distortion   degree

    THD<3% (100% linear load)

    Voltage range

    138~485VAC

    Frequency range

    40-70Hz

    Bypass

    Bypass voltage

    380/400/415VAC

    Voltage range

    Adjustable; 

    220V upper limit: 220V+25% (optional +10%, +15%, +20%) 230V+20% (optional +10%, +15%)
      240V+15% (optional +10%) 

    Lower limit: -45% (optional-10%, -20%, -30%)

    Bypass frequency range

    50/60Hz (lock) ±1Hz, ±3Hz, ±5Hz

    Voltage

    Voltage range

    ±180~±300Vdc (30-50 knots even number adjustable, default 40 knots)

    Output

    Output power factor

    1

    Rated output voltage

    380/400/415VAC

    Rated output frequency

    50/60Hz

    Outputvoltage harmonic distortion

    <2% (linear load), <5% (nonlinear load)

    Inverter overload

    110%, after 1 hour; 125%, 10 minutes; 150%,1 minute;

    >150%, 200ms

    System

    Efficiency

    95.50%

    Levels of protection

    IP 20

    Communication interface

    RS485, dry contact SNMP card, EPO

    Running temperature

    0-40c

    Storage temperature

    -25℃~70℃

    Relative humidity

    0-95% (no condensation)

    Distributing

    Input mode

    Single MCCB / dual ATS input (optional)

    Input specification

    400A

    UPS distributing

    250A*3, MCCB

    IT distributing

    32A/1P*48, MCB

    Power distribution

    63A/3P*8,16A/1P*3, MCB

    Size

    Depth×width×high (mm)

    1100×600×2000 or 1200×600×2000

    * The above parameters may be adjusted and changed, please refer to the physical object.

     