• MP series modular UPS from 20 ~ 720 kVA
    Basic Features

    This product covers a wide range, from computer equipment to communication systems and automatic equipment.

    1. High-reliability design 

    Ultra-wide input voltage range 138~485 Vac (phase voltage 80~280 Vac), use above 305 Vac

    2. Energy saving and green environmental protection

    High input PF value, up to 0.99 , three-level topology structure, the whole machine efficiency is up to 96.5%

    3. Parallel redundancy function

    Direct parallel machine, 6 parallel ,support parallel machine sharing battery pack

    4. Flexible battery configuration scheme

    30~50 optional · single large capacity charging power, to meet the backup requirements of long delay

    5. Super-loading capacity

    Output power factor 0.9 / 1, can take 100% unbalanced load,load adaptability, can be near full load of pure perceptual load and capacitive load

    6. Compatible with generator operation

    Power Walk In Function, reduce the impact current of the system start, reduce the demand of the generator capacity of the parallel system

    7. The LBS synchronization function 

    With LBS synchronization function, to achieve two sets of independent UPS system synchronization, improve the reliability of the system

    8. Intelligent management function 

    Support RS485, SNMP, dry contact and CAN interface

     

    Technical Specifications

     

    Model(maximum capacity)

    MP200kVA/MP300kVA/MP400kVA/MP500kVA/MP600kVA/MP720kVA

    Capacity

    UPS   cabinet

    20-200kVA/30-300kVA/40-400kVA/50-600kVA/60-720kVA

    Module

    20kVA/30kVA/40kVA/50kVA/60kVA

    Main road input

    Input mode

    Three-phase, four-wire + grounding

    Rated voltage

    380/400V/415VAC

    Voltage range

    138-485VAC; 305-485VAC (not decreased); 138-305 VAC)

    Frequency range

    40~70Hz

    Power factor

    0.99

    Input current harmonics

    3%   (100% linear load)

    Bypass input

    Input voltage

    380/400/415VAC

    Bypass range

    Upper bypass protection voltage: +25% (optional +5%, +10%, +20%)

    Lower bypass protection voltage limit: -45% (optional -20%, -30%)

    The wiring system

    Three phase five line

    Bypass   synchronization tracking range (Hz)

    50/60±10%

    Power Walking In

    Support

    Bypass anti-port

    Support

    Generator access

    Support

    Output

    Rated voltage

    380/400/415VAC±1%

    Power factor

    0.9/1.0

    Voltage accuracy

    ±1%

    Output   frequency

    Main   mode

    Synchronized with input; the output frequency is 50/60 (±0.2% Hz when the mainmax exceeds ±10% (±1%, ±2%, ±4%, ±5% are set)

    Battery   mode

    50/60(±0.1%)Hz

    The load peak ratio

    3:1

    Switching period

    Municipal mode to bypass mode: 0ms (tracking); 

    municipal mode to battery mode: 0ms

    Overload capacity

    Load≤110%, 60min, 125%, maintained for 10min, and 150% for 1min

    Output voltage distortion

    ≤2% linear load

    With<4% nonlinear load

    Efficiency

    Normal mode

    ≥96.5%

    Communication interface

    UPS cabinet

    RS232, RS485,2 Intelligent Slot (smart card slots), dry contact

    Battery

    Battery voltage

    ±180~±300Vdc (optional in 30~50 sections)

    Work environment

    Working temperature

    -10℃~45°℃

    Relative humidity

    0~95%   with no condensation

    Storage temperature

    -20℃~65°℃

    Altitude

    <1500m

    Noise (DB)

    <70 (at 1 m)

    Physical   characteristics

    20/30/40kVA
      3 Module cabinet

    20/30/40kVA
      5/6 Module cabinet

    20/30/40kVA
      10 Module cabinet

    50/60kVA
      10/12 module cabinet

    Size   W×D×
      H(mm)

    UPS   system cabinet

    600×840×1400

    600×840×1400

    600×1100×2000

    1200×850×2000

    Module

    440×580×13086

    440×620×130

    Weight   (Kg)

    UPS   system cabinet

    157

    169

    306245

    435/510

    Module

    3221

    33

    Executive standards

    Executive standards

    CE, EN/EC 62040-2EN/IEC 62040-1-1YD/T2165-2017

    The above parameters may be changed, please meet the international EMC safety regulations

     